HSPV-300x Inverter is the driver to communicate with Inverter of Hansol technics Co., Ltd. in Korea.
<Figure 1> is read setting example of HSPV-300x Inverter communication driver.
![]() |
<Figure 1> Read setting example of HSPV-300x Inverter communication driver |
Device part of <Figure 1> input Com port( COM1 ), Baud rate( 19200 ), Parity bit( 0 ), Data bit( 8 ), Stop bit( 1 ) respectively according to controller.
Read schedule of HSPV-300x Inverter communication driver
Read schedule setting parameters are as follows:
1) station – 0 ~ 255 station number.
2) read command – 1P, 3P. ( 1P : single phase, 3P : 3 phase, refer to <Table 1> )
3) read address – don't care.
4) Save start address for Communication Server – Saving start address of Communication Server.
5) Read size – fixed to 1.
Read schedule example)
READ, 1, 1P, 0, 0, 1,
<Table 1> is data saving address and readed value for each read command of Heating HSPV-300x Inverter.
<Table 2> is H/W, S/W Fault data of each bit.
Read command |
Contents | Data saving value of Communication Server |
Remarks |
1P |
1P READ DATA |
Saving Start Address + 0 : communication status (06h : normal, 15h : error) Saving Start Address + 1 : readed Phase (11h : single phase, 33h : 3 phase) Saving Start Address + 2 : Error code(00h : normal, E1h : ENQ error, E2h : Kind error, E3h : check sum error, E4h : port error) Saving Start Address + 3 : present amount of Generation(Word unit) Saving Start Address + 4 : today amount of Generation(Double Word unit) Saving Start Address + 5 : total amount of Generation(Double Word unit) Saving Start Address + 6 : input voltage A (Word unit) Saving Start Address + 7 : input current A (Float unit, 1 dot) Saving Start Address + 8 : input voltage B (Word unit) Saving Start Address + 9 : input current B (Float unit, 1 dot) Saving Start Address +10 : input voltage R (Word unit) Saving Start Address +11 : input current R (Float unit, 1 dot) Saving Start Address +12 : input voltage S (Word unit) Saving Start Address +13 : input current S (Float unit, 1 dot) Saving Start Address +14 : input voltage T (Word unit) Saving Start Address +15 : input current T (Float unit, 1 dot) Saving Start Address +16 : H/W Fault data( 16 bit status value, refer to <Table 2> ) Saving Start Address +17 : S/W Fault data( 16 bit status value, refer to <Table 2>) |
when communication status = 06h and Error code = 0 only save Saving Start Address + 3 ~ Saving Start Address +17 data |
3P |
3P READ DATA |
||
<Table 1> data saving address and readed value for each read command of Heating HSPV-300x Inverter |
bit |
Contents of Fault |
15 ( F ) | Output DC Current |
14 ( E ) | reserved |
13 ( D ) | Over Temperature |
12 ( C ) | Leakage Current |
11 ( B ) | Under Frequency |
10 ( A ) | Over Frequency |
9 | Boost IBGT Fault |
8 | Inverter IBGT Fault |
7 | Output Under Voltage |
6 | Output Over Voltage |
5 | Output Over Current |
4 | DCLink Under Voltage |
3 | DCLink Over Voltage |
2 | Input Under Voltage |
1 | Input Over Voltage |
0 | Input Over Current |
<Table 2> H/W, S/W Fault data of each bit |
HSPV-300x Inverter communication driver store the same data in WORD, DWORD, FLOAT, DOUBLE, INT64 memory, but the data format are different.
If you click the icon
in protocol option part at
<Figure 1>, you
can see the dialog box such as <Figure 2>. you can also set read schedule by
using this part.
![]() |
<Figure 2> Example of Heating HSPV-300x Inverter communication driver¡¯s Option dialog box |
You can set read schedule by using
,
,
button and listbox of <Figure
2>.
![]() |
<Figure 3> Example of HSPV-300x Inverter communication driver¡¯s read schedule Add/Edit dialog box |
When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.
HSPV-300x Inverter communication driver don't support 'write settings'.